Principles of operating the
Greenstar Plus Hybrid Manager
Temperature
Sensor
1
2
4
3
FW200 Weather
Compensation Controller
Greenstar Plus
Hybrid Manager
Greenstar EMS gas-fired
or LPG condensing boiler
Greenstar Plus Hybrid heat pump
➊ Data is inputted into the FW200 controller
•
Calculation of system flow set temperature
•
The appropriate strategy is chosen
– Strategy 1: Cost optimised
– Strategy 2: CO
2
optimised
– Strategy 3: Changeover temperature
– Strategy 4: CO
2
: cost mix.
•
Enter energy price ratio electricity/gas
➋ Greenstar Plus Hybrid Manager:
•
Calculation of flow set temperature for the heat pump
•
Calculation of flow set temperature for the boiler
Function:
Based on required system flow set temperature, ambient
temperature, energy price ratio and/or primary energy
factors the overall highest possible system efficiency
is calculated.
➌ Boiler: (the higher temperature heating option)
•
Supports central heating up to the calculated flow
set temperature for the system or supports all DHW
demand. Alternatively it can remain turned off.
➍ Heat pump: (the lower temperature heating option)
•
Supports central heating up to the calculated flow
set temperature for the heat pump (boiler turns
on to reach peak demand) or supports 100% of
the central heating up to the required system flow
set temperature (so the boiler remains turned off).
Alternatively the heat pump can remain turned off.